Holdvolt H33-Li

High-Power Lithium-ion UPS, 200–600 kVA

Large-frame double conversion matched to high-voltage lithium battery cabinets.

200–600kVA
Cabinet
1
Output PF (kVA = kW)
≥97%
System efficiency
<2%
Input THDi

How it works

Mains lost. The load does not notice.

0 ms
mains to battery
DC bus
battery always connected
Inverter
load never sees the grid
Battery feeds the DC bus; the inverter keeps the load running.

Conversion

  • Online double conversion
  • DSP control
  • Active PFC, input PF ≥0.99
  • ECO mode

Grid and generator

  • Wide input voltage
  • Generator compatible
  • 50 / 60 Hz auto-sensing
  • 7-inch display

Battery

  • Adjustable battery quantity
  • Multi-stage charging
  • Cold start on battery

Monitoring

  • LCD panel
  • RS-232 / USB
  • SNMP card (option)
  • EPO

Specifications

Factory catalog values, model by model.

200–600 kVA

ModelH33-200K-LiH33-300K-LiH33-400K-LiH33-500K-LiH33-600K-Li
Other
Capacity 200KVA/200KW300KVA/300kW400KVA/400KW500KVA/500kW600KVA/600KW
IP rating IP20
Input
Wiring 3Ph+N+PE
Input voltage 380/400/415 VAC (line); 220/230/240 VAC (phase)
Input Frequency 50/60Hz
Power factor >0.99
THDi THDi<2%(100%linear load)
Voltage range 304–478 VAC (line) full load; 228–304 VAC (line) linear derating (load 100% → 50%)
Frequency range 40-70Hz
Battery
Battery voltage 3-wire: ±240 VDC (30–50 cells adjustable); Optional 2-wire: 480 VDC (30–50 cells adjustable)
Charging power Max. 20% × active power
Charging voltage accuracy ±1%
Bypass
Bypass voltage 380/400/415VAC(line) ; 220/230/240VAC(phase)
Voltage range Adjustable; default -20% to +15%; Upper limit: +10% / +15% / +20% / +25%; Lower limit: -10% / -15% / -20% / -30% / -40%
Overload capability 125%: continuous; 125% < load < 130%: ≥ 10 min; 130% < load < 150%: ≥ 1 min; >150%: 300 ms110%: continuous; 101% < load < 125%: ≥ 5 min; 125% < load < 150%: ≥ 1 min; >150%: 1 s110%: continuous; 101% < load < 125%: ≥ 5 min; 125% < load < 150%: ≥ 1 min; >150%: 1 s110%: continuous; 101% < load < 125%: ≥ 5 min; 125% < load < 150%: ≥ 1 min; >150%: 1 s110%: continuous; 101% < load < 125%: ≥ 5 min; 125% < load < 150%: ≥ 1 min; >150%: 1 s
Output
Rated output voltage 380/400/415VAC(line);220/230/240VAC(phase)
Rated frequency 50/60Hz
Power factor 1
Voltage accuracy ±1.0%
Dynamic voltage response <5%(20%-80%-20%step load)
Recovery time <20ms(0%-100%-0%step load)
Output THDu <1%(linear),<5%(non-linear)
Frequency accuracy 0.1%
Sync tracking range Adjustable:±0.5 Hz to ±5 Hz (default ±3 Hz)
Sync tracking rate Adjustable: 0.5–3 Hz/s (default 0.5 Hz/s)
Crest factor 3:1(max)
3-phase accuracy 120°±0.5°
Overload
Inverter overload 110%: transfer to bypass after 1 h; 125%: after 10 min; 150%: after 1 min; >150%: after 200 ms
Efficiency
System Efficiency Main mode ≥ 97%; Battery mode ≥ 97%
Display & communication
Display LCD+LED+7-inch displayLCD+LED+10-inch displayLCD+LED+10-inch displayLCD+LED+10-inch displayLCD+LED+10-inch display
Options SNMP card, dry contacts card, parallel kit, lightning protection kit, top air outlet kit, APP WiFi/Bluetooth
Physical
Cable entry Front top entry; optional front bottom entryFront top entry; optional front bottom entryCompatible with top/bottom entryCompatible with top/bottom entryCompatible with top/bottom entry
Cabinet (W×D×H) mm 600×750×1600600×750×2000600×850×20001200×850×20001200×850×2000
Module (W×D×H) mm 440×475×140
Environment
Working environment 0–40°C (operating); -25–70°C (storage); 0–95% RH (non-condensing)
Noise (1 m in front) 68 dB @ 100% load; 65 dB @ 45% load

Factory values. Specifications may change; confirm against the quotation.Swipe the table sideways.

Where it fits

Applications and guides for this range.

Questions buyers ask

What do you need for a quotation?

Load in kVA or kW, input voltage and phases, output phases, the backup time you need and where the unit will be installed. If you are unsure, send what you know and we will ask for the rest.

Can the unit carry our brand?

Yes. Logo, front panel, packaging and manual can be supplied under your brand. Minimum quantities and lead times are on the OEM / ODM page.

More in Lithium-ion UPS

Five numbers get you a quote

Send what you know. We reply within one working day.

  1. LoadkVA or kW, and what it is
  2. Input voltage and phasese.g. 400 V three-phase, 50 Hz
  3. Output phasesSingle- or three-phase
  4. Backup timeMinutes at full or typical load
  5. SiteIndoor, temperature, altitude, generator