Sizing & Selection · 2 min read · · Holdvolt team

kVA vs kW in an Online UPS: How to Read the Power Factor on a Datasheet

Two ratings sit side by side on every datasheet, and a load has to fit inside both. Here is how to read them, with worked examples where each one becomes the limit.

Three-phase online UPS cabinet and battery cabinets in an electrical room

A 100 kVA unit is not always a 100 kW unit. The gap between those two numbers is the output power factor, and it is one of the most common reasons a system that looked right on paper overloads at commissioning.

What the two numbers mean

kVA is apparent power: voltage times current. It sets how much current the inverter and cables have to carry. kW is real power: what the load actually consumes and turns into work and heat. It sets how hard the power stage and the battery have to work.

They are linked by power factor (PF):

kW = kVA × PF

RatingOutput PFReal power available
10 kVA1.010 kW
10 kVA0.99 kW
100 kVA0.880 kW
100 kVA1.0100 kW

The same nameplate kVA can deliver 25% more real power on a unit with output PF 1.0 than on one with 0.8. Comparing quotes on kVA alone hides that difference.

A load has to fit inside both ratings

Check the load against each rating separately. Which one runs out first depends on the power factor of the load compared with the output power factor of the unit.

Case 1: kW runs out first

A 100 kVA unit with output PF 0.8 gives 80 kW. A server load of 85 kW at PF 0.99 draws about 86 kVA. It looks fine against the 100 kVA headline, but it is over the 80 kW limit by more than 6%.

Case 2: kVA runs out first

A 100 kVA unit with output PF 1.0 gives 100 kW. A motor-heavy load of 80 kW at PF 0.7 draws about 114 kVA. There is plenty of real power to spare, but the current limit is exceeded.

What this means for current

Cable, breaker and busbar sizes follow kVA, because they carry current whatever the power factor. For a quick figure:

  • Single-phase: I = S ÷ V
  • Three-phase: I = S ÷ (√3 × V)
RatingVoltageFull-load output current
10 kVA, single-phase230 Vabout 43 A
30 kVA, three-phase400 Vabout 43 A
100 kVA, three-phase400 Vabout 144 A
400 kVA, three-phase400 Vabout 577 A

Input current is higher than these output figures once inverter losses and battery recharge are included, so size the input side from the input current on the datasheet.

Questions to ask before you compare quotes

  1. What is the output PF at the rated load, and at what ambient temperature?
  2. Is the kW rating still valid with the load power factor you actually have?
  3. Does the rating change with battery recharge running at the same time?
  4. Is the per-phase rating enough on your most heavily loaded phase?

For the full method, including margin, inrush and runtime, see how to size an online UPS. Rated ranges are listed under online UPS systems.

Keep reading

All posts

Specifying a UPS for a project?

Send the load, voltage, phases and backup time. We reply within one working day with a configuration and a quote.

Request a quote See the range